CAREL ir33

Quick reference Handbook

Ver. 1.1 Eng Pag.1/12

Updated: 17/03/2010

MAIN FEATURES OF THE INSTRUMENT

USER INTERFACE

1. ON/OFF switch button – UP button to increase temperature values2. DOWN button to decrease values - Activates/deactivates the

manual defrost

3. SET temperature button

4. Prg/mute button

5. Malfunctioning or failure warning icon

6. High/Low temperature alarm icon

7. icon is ON when defrost process starts

8. icon is ON when compressor starts 9. icon is ON when evaporator fans starts 10. icon is ON when an auxiliary output is active

Ver. 1.1 Eng Pag.2/12

Updated: 17/03/2010

POWER OFF

When the instruments is switched offthe display shows the label OFF and all internal relays are disabled (not energized)

POWER ON

When the controller is switched on a special procedure tests the display and the keypad. The display is completely ON for 2 seconds

Three segments “---“ on the display are visualized for 2 seconds and then the controller becomes operative

Compressor icons flashesand the compressor activation is delayed by safety times

To display or to set the temperature, proceeds as follows:

Keep SET button pressed for more than 1 second. The instruments displays the temperature value

SET CAVITY TEMPERATURE

Increase or decrease the set point using UP/DOWN buttons, until reaching the desired value

Press SET button again to confirm the new value

Press Prg/mute button more than 5 seconds the instruments shows the code of the first adjustable parameter (type “F”) – if an alarm is active, pressing this button, the buzzer is muted first.

FREQUENTLY USE PARAMETER LIST: St, rd, rt, rH, rL, dI, dt1, dt2, dP1, dP2, dd, d8, d/1, d/2, AL, AH, Ad, F1, Fd

FREQUENT USE PARAMETER (TYPE F)

CONFIGURATION Access to the configuration parameters is protected by password that PARAMETER avoid unwanted modifications or access by unauthorized personel. (TYPE C) Proceeds as follows:

1. Press Prg/Mute and Set buttons together for more than 3

seconds; display shows a flashing numerical code “0” that indicates the password prompt

2. Press UP button to set the password – CAREL thermoregulators are

provided with password set to 11 (the code of the password allows access to the configuration parameters)

mode and scroll up/down the operating parameters list /2

3. Confirm by pressing the Set button to enter in the programming

4. Display shows the code of the first adjustable type “C” parameter

Ver. 1.1 Eng Pag.3/12

Updated: 17/03/2010

MANUAL DEFROST

Manual defrost is activated or deactivated if DEF/DOWN button is keep pressed more than 5 seconds.

When defrost starts display shows dFb (defrost begining)

Defrost’s warning icon is ON when defrost is active

Defrost can be interrupted simply by pressing again the DEF/DOWN button more than 5 seconds. Display shows the message dFE(defrost End)

After having displayed the first operating parameter, either type C or type F, it is necessary to procedes as follows:

1. Press UP/DOWNbutton until reaching the parameter to be

modified. When scrolling the list, an icon appears on the display that indicates the category the parameter belongs to

2. Press SET button to display the parameter’s value

MODIFYING THE PARAMETERS

3. Increase or decrease its value using UP/DOWN button

4. Press again SET button to temporarily save the new value, closing

the parameter adjustment and return to the display of the parameter code

Repeat the operations from point 1 to 4

STORING THE NEW ASSIGNED VALUES

To definitively store the new values of the modified parameters, procede as follows:

1. Press the Prg/mute button more than 5 seconds

2. Display shows the label Pro

The controller step out the parameter setting procedure and the display shows current temperature value.

RESET ANY

MODIFICATIONS

All modifications made to the parameters, temporarily stored into the internally memory of the controller, can be cancelled and normal operation resumed by not pressing any button for 60 second, thus allowing the parameter setting session to expire due to timeout

Ver. 1.1 Eng Pag.4/12

Updated: 17/03/2010

HOW TO CHECK CAVITY PROBE TEMPERATURE

To check current temperature measured by a single installed probe, proceeds as follow:

1. refers to the previous step how to get in the configuration

parameter session - type C parameter

2. scroll the configuration parameter list, by using UP/DOWN

buttons, until display shows the parameter /C1 (calibration or offset for cavity probe) 3. press SET button

4. display shows the probe calibration value, used to correct the

temperature measured by the probe by means of an offset

BE CAREFUL ⇒ DO NOTADJUST THE CALIBRATION VALUE

5. Press again SET button

6. display shows the current temperature value measured by the

probe

7. press SET button to return to display of the parameter code /C1 Current evaporator probe temperature is available by means of the parameter /C2 (calibration or offset for evaporator probe)

To check temperature value proceeds as previously indicated from step 1 to step 2, considering the configuration parameter /C2

HOW TO CHECK EVAPORATOR TEMPERATURE

HOW TO CHECK CONDENSER TEMPERATURE

If the condenser probe is installed it is possible to check condenser temperature by means of the parameter /C3 (calibration or offset for condenser probe)

To check temperature value proceeds as previously indicated from step 1 to step 2, considering the configuration parameter /C3

Ver. 1.1 Eng Pag.5/12

Updated: 17/03/2010

TABLE OF OPERATING PARAMETERS N°

1 2 3 4 5 6 7 8 9 10 11 12 13

Code /2 /3 /4 /5 /6 /tl /tE /P /A2 /A3 /c1 /c2 /c3 St rd rn rr r1 r2 r3 r4 r5 rt rH rL c0 c1 c2 c3 c4 cc c6 c7 c8

Range 0...15 0...15 0…100 0/1 0/1 1…6 0...6 0…2 0…3 0…3 -20…20 -20…20 -20…20 r1…r2 0.1…20 0…60 0.1…20 -50...r2 r1…200 0...2 -20...20 0...1 0...999

- - 0...15 0…15 0...15 0...15 0…100 0…15 0…15 0...900 0...60

U.M. -- -- -- Flag Flag -- -- -- -- --

Description

Measurement stability Probe display response Virtual probe Selection °C or °F Decimal point Display on terminal

Display on external terminal Type of probe Configuration probe 2 Configuration probe 3

TEMPERATURE PROBE MANAGEMENT PARAMETERS

°C/°F (/10) Calibration probe 1 °C/°F (/10) Calibration probe 2 °C/°F (/10) Calibration probe 3 °C/°F set point temperature °C/°F °C/°F °C/°F °C/°F °C/°F Flag °C/°F °C/°F °C/°F °C/°F °C/°F Minutes Minutes Minutes Minutes Minutes Hours Hours Seconds Seconds

Control delta Dead band

Reverse differential for control with dead band Minimum set point allowed Maximum set point allowed Operating mode

Automatic night-time set point variation Enable temperature monitoring Temperature monitoring interval Maximum temperature read Minimum temperature read

Compressor and fan delay on start-up

Minimum time between two sequent compressor

starts

Minimum compressor OFF time Minimum compressor ON time Duty setting

Continuous cycle duration

Alarm bypass after continuous cycle Maximum pump down time

Compressor start delay after open PD valve

TEMPERATURE CONTROL PARAMETERS

14 15 16 17 18 19 20 21 22 23 24 25

COMPRESSOR SAFETY TIME AND ACTIVATION PARAMETERS

26 27 28 29 30 31 32 33 34

Ver. 1.1 Eng Pag.6/12

Updated: 17/03/2010

35 36 37

Code c9 c10 c11 d0 dI dt1 dt2 dtP dP1 dP2 d3 d4 d5 d6 dd d8 d8d d9 d/1 d/2 dC d10 d11 d12 dn dH A0 A1 AL AH Ad A4 A5 A6 A7 A8

Range 0...1 0...1 0...250 0...4 0…250 -50…200 -50…200 0...200 1…250 1…250 0...250 0/1 0…250 0...2 0…15 0…15 0…250 0/1 - - 0/1 0...250 -20...20 0...3 1...100 0...100 0.1…20.0 0/1 -50…200 -50…200 0…250 0…15 0…15 0…100 0…250 0/1

U.M. Flag Flag Seconds Flag Hours °C/°F °C/°F °C/°F Minutes Minutes Minutes Flag Minutes -- Minutes Hours Hours Flag °C/°F °C/°F Flag Hours °C/°F -- % -- °C/°F Flag °C/°F °C/°F Minutes Flag Flag Minutes Minutes Flag

Description

Enable autostart function in PD Select Pump down by time or pressure Second compressor delay Type of defrost

Interval between defrosts

End defrost temperature, evaporator End defrost temperature, aux evap.

Defrost end temperature when defrost has done with compressor OFF and fans ON Maximum defrost duration, evaporator Maximum defrost duration, aux evap. Defrost start delay Enable defrost on start-up Defrost delay on start-up Display on hold during defrost Dripping time after defrost Alarm bypass after defrost Alarm bypass after door open

Defrost priority over compressor protectors Defrost probe 1 read Defrost probe 1 read Time base (0=h/m;1=m/s)

Compressor running time for defrost Running time temperature for defrost Advanced defrost Nominal defrost duration

Proportional factor, variation in dI Alarm (fan) differential Relative or Absolute Alarm Low temperature alarm threshold High temperature alarm threshold Low and high temperature signal delay Digital input 1 configuration Digital input 1 configuration

Stop compressor from external alarm External alarm detection delay Enable alarms ‘Ed1’ and ‘Ed2’

DEFROST MANAGEMENT PARAMETERS

38 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61

ALARM MANAGEMENT PARAMETERS

62 63 65 66 67 68 69 70 71

Ver. 1.1 Eng Pag.7/12

Updated: 17/03/2010

72 73 74 75 76 77 78 79

Code Ac AE Acd AF ALF AdF ACS ACd F0 F1 F2 F3 Fd F4 F5 H0 H1 H2 H4 H6 H8 H9 Hdh CCd Cd SAn SAr CAn CAr

Range 0...200 0.1...20 0…250 0…250 -50...200 0…15 -50...200 0.1...50 0...2 -50...200 0/1 0/1 0…15 -50...200 0.1...20 0…207 0...10 0...6 0/1 0...255 0/1 0/1 -50...200 0...999 0...999 0...255 0...1 0...255 0...1

U.M. °C/°F °C/°F Minutes Seconds °C/°F Minutes °C/°F Minutes Flag °C/°F Flag Flag Minutes °C/°F °C/°F -- Flag Flag Flag -- Flag Flag °C/°F -- -- -- Flag -- Flag

Description

High condenser temperature alarm

High condenser temperature alarm differential High condenser temperature alarm delay Light sensor OFF time Antifreeze alarm threshold Antifreeze alarm delay Alarm Clean Setpoint Alarm Clean differential Fan management Fan stop temperature

Fan OFF with compressor OFF Fans in defrost Fan OFF after dripping

Condenser fan stop temperature Condenser fan start differential Serial address Function of relay 4 Disable keypad/IR Disable buzzer Lock keypad

Select activation of output with time band Enable set point variation with time band Anti-sweat heater offset Clean Counter Days Clean days

Service Alarms number

Service Alarms counter reset San Clean Alarm counter Clean Alarm counter reset

EVAPORATOR FAN MANAGEMENT PARAMETERS

81 82 83 84 85 86 87

GENERAL CONFIGURATION PARAMETERS

88 90 91 92 93 94 95 96 97 98 99 100 101

NOTE 1:

Above operating parameters are available for all range of CAREL thermoregulators. Particularly all green highlighted parameters are available on new CAREL controller ir33 IRELF0HN245, currently installed on HD cabinets and counters

NOTE 2:

Blu highlighted operating parameters listed above are not influential for the functioning of the appliance.

Ver. 1.1 Eng Pag.8/12

Updated: 17/03/2010

SERVICE ALLARMS AND SIGNALS SERVICE ALARMS

SERVICE ALARMS DUE TO MALFUNCTIONING OR FAILURE PRODUCE A WARNING SIGNALS ON THE DISPLAY BY MEAN OF THE SERVICE ICON

CAVITY PROBE FAULT

In case of cavity probe faulty or malfunctioning display shows the error signal rE and E0 (cavity probe S1 fault) alternately

The appliance works however and compressor starts are controlled by time (15 mins is ON and 15 mins is OFF) until the fault is resolved.This alarm signal is automatically restored when the faulty erased and the probe replaced

During this time interval the service alarm icon flashes on display and an acoustic signal is ENABLED

In case of evaporator probe faulty or malfunctioning display shows an error signal E1 (evaporator probe S2 fault).

This alarm signalis automatically restored when the faulty erased and the probe replaced

EVAPORATOR PROBE FAULTY

During this time interval the service alarm icon flashes on display. Acoustic signal is DISABLED

CONDENSER In case of condenser probe faulty or malfunctioning display shows the PROBE FAULTY error signal SEr and E2 (condenser probe S3 fault) alternately (WHEN INSTALLED ON BOARD)

This alarm signalis automatically restored when the faulty erased and the probe replaced

During this time interval the service alarm icon flashes on display. Acoustic signal is DISABLED

If a probe is set as the condenser probe, the condenser temperature can be monitored to signal the high temperature alarm, due to obstruction or fouling

In this case a warning signal is visualized and display shows the error signal CLn and the temperature measured by the condenser probe alternately

CLEAN ALARM

Service alarm icon is flashing and the acoustic signal DISABLED

The clean alarm is reset to zero by pressing the Prg/mute button and the service alarm icon cancelled on display

Ver. 1.1 Eng Pag.9/12

Updated: 17/03/2010

TEMPERATURE ALARMS AND SIGNALS TEMPERATURE ALARMS

HIGH OR LOW TEMPERATURE ALARMS DUE TO MALFUNCTIONING OR COMPONENTS FAILURE PRODUCE A WARNING SIGNALS ON THE DISPLAY BY MEAN OF THE ALARM ICON.

LOW

TEMPERATURE ALARM

In case of low cavity temperature, referred to the cavity probe, the display shows a flashing error code LO.

Temperature alarm icon is flashing and the acoustic signal ACTIVE.

This alarm is automatically reset when cavity temperature increase over the minimum temperature threshold, depending from the parameter AL

HIGH

TEMPERATURE ALARM

In case of high cavity temperature, referred to the cavity probe, the display shows a flashing error code HI.

Temperature alarm icon is flashing and the acoustic signal ACTIVE.

This alarm is automatically reset when cavity temperature decreaseunder the maximum temperature threshold, depending from the parameter AH

In case of condenser fan faulty ormalfunctioning display shows a flashing error code SEr

Temperature alarm icon is flashing and the acoustic signal ACTIVE

Pressing Prg/mute button the buzzer is DISABLED but the alarm signal is still active and shown on the display

CONDENSER FAN ALARM

Ver. 1.1 Eng Pag.10/12

Updated: 17/03/2010

CONNECTIONS Follows all electrical connections available on ir33 CAREL controller , currently used in production

IRELC0HN215 (6R05100) Æ installed on STD BEN and CL freezer counter and STD BEN cabinet provided with internal light

IRELF0EN215 (6R04700) Æ installed on all STD BEN refrigerated counters, 400Lt refrigerated cabinets and all STD BEN cabinets without light

Ver. 1.1 Eng Pag.11/12

Updated: 17/03/2010

IRELF0HN245 (6R09300) Æ installed on HD counters and cabinets

IRELF0EN225 Æ installed on digital ROLL–IN

IRELF0EHD15 Æ installed on 400Lt FREEZER cabinet

Ver. 1.1 Eng Pag.12/12